Разширители

EKL M1XIN M1 16 Zone Input Expander

razshiriteli M1XIN16 Zone Input Expander

Adds 16 hardwired zones (EOL resistor supervised) to the M1 Gold or M1EZ8 Controls. Operates from 4-wire data bus. Up to 12 of these can be used, increasing total zones (inputs) to 208.

Features:

• 16 EOL Resistor Supervised Hardwire Zones
• Operates on the 4-Wire Data Bus
• DIP Switch Address Settings
• Flash Memory for Firmware Updating
• Plug-In Terminal Strips
• Status and Diagnostic LED
• On-Board EOL Bus Termination Jumper
• Vertical Mounting using ELK-SWG Glides(included)

Specifications:

• Inputs: Plug-In Terminals with Elevator Style Wire Clamps and Screws
• Operating Power Range: 9 to 14 VDC
• Current Draw: 65 mA
• Size: 6″ x 3.25″ x .75″ H

Installation guide in PDF format


ELK-M1XOV M1 16 Output Expander, Flying Voltage Leads

razshiriteli M1XOVM1 16 Output Expander,

Adds 16 voltage outputs to M1 Gold or M1EZ8 Controls. Provides 2 plug-in, 8-pin flying lead connectors for triggering low current devices (50 mA max. each such as: LEDs, relays, piezos, etc. Operates from 4-wire data bus. Up to 12 Output Expanders may be used for a total of 208 outputs. The voltage outputs can be converted to relays (8 or 16) using (1 or 2) M1RB Relay Board(s).

FEATURES:

16 Voltage Outputs
Operates on the 4-Wire Data Bus
DIP Switch Address Settings
Flash Memory for Firmware Updating
Two (2) – Twelve (12) Conductor „Flying Lead“ Wire Harnesses
Voltage Outputs may be converted to Relays using M1RB Relay Boards
Status LED with Diagnostic Display
Mounts in Enclosure using ELK-SWG Glides, SWP3 Structured Wire Plate, or Double Sided Foam Tape

SPECIFICATIONS:

Outputs: 12 VDC @ 50 mA each
Wire Harness Length: 12″
Operating Power Range: 9 to 14 VDC
Current Draw: 65 mA Nom., 330 mA Max.
Size: 6″ x 3.25″ x .75″ H

Installation guide in PDF format


ELK-M1XOVR M1 16 Output Expander, 8 Voltage & 8 Relays

razshiriteli M1XOVRM1 16 Output Expander, 8 Voltage & 8 Relays

Adds 16 outputs (8 voltage, 8 relays) to M1 Gold or M1EZ8 Controls. Voltages can be used to trigger low current devices (50 mA max. each). Relays are SPDT rated for 7A @ 30 VDC, 10A @ 125 VAC. Operates from 4-wire data bus. Up to 12 output expanders may be used for a total of 208 outputs. Option: Convert 8 voltage outputs to relays using M1RB Relay Board.

 

FEATURES:

8 Voltage Outputs
8 Single-Pole, Double-Pole Relay Outputs
Operates on the 4-Wire Data Bus
DIP Switch Address Settings
Flash Memory for Firmware Updating
One (1) – Twelve (12) Conductor „Flying Lead“ Wire Harness
Voltage Outputs may be converted to Relays using M1RB Relay Boards
Status LED with Diagnostic Display
Mounts in Enclosure using ELK-SWG Glides, SWP or SWP3 Structured Wire Plates, or Double Sided Foam Tape

SPECIFICATIONS:

Voltage Outputs: 12 VDC @ 50 mA each
Relay Outputs: SPDT rated for 7 Amps @ 28VDC, 10 Amps @ 125 VDC
Wire Harness Length: 12″
Operating Power Range: 9 to 14 VDC
Current Draw: 65 mA Nom., 330 mA Max.
Size: 6″ x 3.25″ x .75″ H

Installation guide in PDF format


ELK-M1XSP M1 Serial Expander, Lighting/Thermostat Interface

razshiriteli M1XSPSerial Ezpander

This is a „3 in 1“ product for additional serial ports and for integration with lighting systems and thermostats. Jumpers on the M1XSP select the appropriate application, connection, and protocol. Best of all, the M1XSP operates from the 4-wire (RS-485) M1 Keypad data bus, allowing RS-232 ports to be located long distances from the control. The M1 Gold and M1EZ8 support up to 7 M1XSPs. The communications baud rate is adjustable from 300 to 38,400 baud. The unit comes complete with cable and a black surface mountable housing.

 

FEATURES:

Adapts the M1 to various Lighting control products which use „serial“ communications. I.E.,OnQ-ALC, PCS-UPB, Centralite, etc.
Adapts HVAC Communicating Thermostats from RCS, Aprilaire, and HAI to the M1 Cross Platform ControlÒ
Expands the RS-232 Serial Ports of the M1 Control
Operates from the M1 Data Bus
DIP Switch Address Settings
Jumper Options and LED Diagnostic indicator
On-Board EOL Bus Termination Jumper
Flash Memory for Firmware Updating

SPECIFICATIONS:

Maximum Expandable Ports (Units)
ELK-M1G Gold – 7
ELK-M1 (Std) – 1
Operating Voltage: 12 Volts D.C.
Current Draw: 31mA
Housing Dimensions: 4.375″ x 3.0″ x 1.125″
Circuit Board Dimensions: 3.5″ x 2.75

Installation guide in PDF format


ELK-M1RB M1 Relay Board, Plug-in (8 form ”C” relays)

releini moduli M1RBRelay Board

May be plugged directly into an M1G, M1EZ8, M1XOV, or M1XOVR to convert the voltage outputs into SPDT relays rated for 7A @ 30 VDC, 10A @ 125 VAC.

FEATURES:

8 Form „C“ Relays, SPDT Dry Contact
Heavy Duty Contact Rating
Low Current Draw.
Great For General Purpose Switching.
Plug-in „Removable“ Terminal Blocks
LED Status Indicators on all 8 Relays
Twelve (12) Conductor Plug-in Wire Harness
Mounts in Enclosure using ELK-SWG Glides

SPECIFICATIONS:

Diode Protection Across Relay Coil.
Contact Ratings:
7 Amps @ 28 VDC, 10 Amps @ 125 VAC
Wire Harness Length: 24″
Operating Voltage: 12 Volts DC Nominal
Current Draw: 0 mA idle, 250 mA Max.
Size: 6″ x 3.25″ x .75″ H

Installation guide in PDF format